What are the range hood and bathroom fan rules for a remodel in Los Angeles?

By Home Pro Green Remodeling Inc. · Published November 23, 2026

What are the range hood and bathroom fan requirements in California?

California's Energy Code requires a local exhaust fan in each kitchen and bathroom: a bathroom fan must move at least 50 cfm when switched on (or 20 cfm if it runs continuously), and a range hood covered by the code must meet an airflow or capture efficiency rating set by the home's floor area and the range fuel type.1 In a remodel, a bathroom fan that is altered or replaced must meet those rules, while a kitchen hood depends on what the home's earlier permits required.2

Home Pro Green Remodeling Inc. is based in Tarzana and serves the San Fernando Valley and greater Los Angeles. This page summarizes the published state code and City permit lists. It is not a Home Pro quote or schedule. Your permit and your equipment's ratings decide what applies.

Which code sets the rules?

Title 24, Part 6 (the Energy Code), Section 150.0(o), which adopts ASHRAE Standard 62.2 with California amendments.1 Buildings whose permit applications are applied for on or after January 1, 2026 must comply with the 2025 Energy Code.3 In the City of Los Angeles, the permit comes from LADBS.

What does a bathroom exhaust fan need?

  • Fan that runs when switched on: at least 50 cfm.1
  • Fan that runs continuously: at least 20 cfm.1
  • Controls: a switched fan needs a readily accessible on-off control the occupant can use, or an automatic control that does not stop the occupant from turning it on. A continuous fan needs a readily accessible manual on-off control.1
  • Ratings: new or replacement fans must be rated for airflow and sound under ASHRAE 62.2, and a replacement fan must be rated at no less than the airflow the code requires.2

If your bathroom remodel alters the exhaust fan, the altered system has to meet these requirements.2

What does a kitchen range hood need?

For a vented range hood, Table 150.0-G sets either a capture efficiency (CE) rating or an airflow, by the home's floor area and the fuel the range uses:1

  • Over 1,500 sq ft: electric range 50% CE or 110 cfm; gas range 70% CE or 180 cfm.
  • Over 1,000 to 1,500 sq ft: electric 50% CE or 110 cfm; gas 80% CE or 250 cfm.
  • 750 to 1,000 sq ft: electric 55% CE or 130 cfm; gas 85% CE or 280 cfm.
  • Under 750 sq ft: electric 65% CE or 160 cfm; gas 85% CE or 280 cfm.

Other kitchen exhaust fans, including downdraft units, need 300 cfm when switched on. An enclosed kitchen with a continuous fan needs 5 air changes per hour, based on the kitchen's volume.1

Do you have to upgrade the range hood when you remodel the kitchen?

It depends on the home's permit history. If the kitchen fan is altered or replaced, the 2025 code gives three cases:2

  1. If an earlier permit required the home to meet the kitchen exhaust rules in 150.0(o)1G, the new fan must meet them too.
  2. If an earlier permit required a vented range hood or other kitchen exhaust fan, the replacement must meet the airflow that permit required, or 100 cfm, whichever is greater.
  3. If neither applies, the kitchen exhaust rules in 150.0(o)1G are not required.

The California Energy Commission says replacing a vented range hood alone, on the existing ducts, does not require ECC-Rater field verification. A new vented range hood with an entirely new duct system must meet Section 150.0(o), which includes ECC-Rater field verification.4

What counts as an entirely new duct system?

The code treats a ventilation system as entirely new when it has a new fan and a duct system built from at least 75 percent new duct material.2 For new ducts, the fan's airflow is either measured on site or assumed from its certified rating when the duct sizes meet Table 150.0-H. For example, a fan rated up to 250 cfm needs at least an 8 inch rigid duct under that table.1

Which LADBS permit covers a new fan or hood duct?

LADBS lists both on its Express Permit bulletin, with no plan check: adding general ventilation exhaust fans rated 2,000 cfm or less, and duct work alterations in buildings without a smoke control system.5 Electrical work under 600 volts and up to 400 amps total load in an existing home is also on the Express list.5 Our posts on kitchen remodel permits and bathroom remodel permits in Los Angeles cover the rest of the permit.

What should you ask before you buy a hood or fan?

  • Is the hood vented to the outside, and will it reuse the existing duct or need a new one?
  • What airflow or capture efficiency rating does it list, and does that meet Table 150.0-G for your home's size and range fuel?
  • What duct size will be used?
  • Does the work need ECC-Rater field verification, and who arranges it?
  • Is the bathroom fan switched or continuous, and where is the control?

What should the contract say?

CSLB says a contract should detail the work, the price, when payments will be made, who gets the necessary building permits, and when the job will be finished.6 Check the license on the CSLB Check a License page.7 Ours is 1003187. We pull the permits, and the contract should name who does.

Written by Home Pro Green Remodeling Inc., a general contractor in Tarzana with over 30 years of combined experience. CSLB #1003187.

Next step

Call (213) 770-6727 or use the contact form to talk about your kitchen or bathroom remodel. We will look at the existing hood, fan and ducts and what the permit will cover. Home Pro Green Remodeling Inc., CSLB #1003187.

Related reading

Home Pro Green Remodeling Inc. | CSLB #1003187 18375 Ventura Blvd Ste 378, Tarzana, CA 91356 (213) 770-6727

Sources (all pages opened and read on 2026-11-23)

  1. California Energy Commission, CF2R-MCH-32-H Local Mechanical Exhaust, 2025 Single-Family Compliance, Jan 1, 2026 (Section 150.0(o) and ASHRAE 62.2; a local exhaust fan in each kitchen and bathroom; Tables 150.0-E, 150.0-F, 150.0-G and 150.0-H; control requirements). https://www.energy.ca.gov/filebrowser/download/8693?fid=
  2. Energy Code Ace (California statewide utility program), 2025 Energy Code Section 150.2 text (150.2(b)1L entirely new or complete replacement ventilation systems; 150.2(b)1M altered systems: bathroom and kitchen local exhaust, replacement fans). https://energycodeace.com/content/cy25-mechanical-ventilation-for-indoor-air-quality-altered-ventilation-systems.
  3. California Energy Commission, 2025 Building Energy Efficiency Standards (permit applications on or after January 1, 2026 must comply). https://www.energy.ca.gov/programs-and-topics/programs/building-energy-efficiency-standards/2025-building-energy-efficiency
  4. California Energy Commission, 2025 Single-Family HVAC frequently asked questions (range hood replacement on existing ducts; new hood with entirely new duct system). https://www.energy.ca.gov/programs-and-topics/programs/building-energy-efficiency-standards/energy-code-support-center/hvac-0
  5. LADBS Information Bulletin P/GI 2026-003, Express Permits (No Plan Check Required), effective Jan 1, 2026, revised Jun 10, 2026 (HVAC items 7 and 11; electrical item 1). https://dbs.lacity.gov/sites/default/files/efs/forms/pc17/ib-p-gi-2020-003-express-permits_rev-5-28-2024.pdf
  6. CSLB, Contracts and Binding Agreements (a contract should detail the work, price, payments, who gets the building permits, and when the job will be finished). https://www.cslb.ca.gov/consumers/hire_a_contractor/Contracts_And_Binding_Agreements.aspx
  7. CSLB, Check a License. https://www.cslb.ca.gov/onlineservices/checklicenseII/checklicense.aspx

Frequently asked questions

Is a bathroom exhaust fan required in California?

Yes. The Energy Code requires a local exhaust fan in each bathroom, at least 50 cfm when switched on or 20 cfm running continuously.

What size range hood is required in California?

It depends on the home's floor area and the range fuel. For a home over 1,500 square feet, a hood over an electric range needs 50% capture efficiency or 110 cfm, and over a gas range 70% or 180 cfm.

Do I need to upgrade my range hood when I remodel my kitchen?

Only in some cases. It depends on what the home's earlier permits required; if a vented hood was required, the replacement must meet that airflow or 100 cfm, whichever is greater.

Does replacing a range hood need ECC-Rater verification?

Not when the hood alone is replaced on the existing ducts. A new hood with an entirely new duct system does.

Does a new exhaust fan need a permit in Los Angeles?

Yes. Adding a general ventilation exhaust fan rated 2,000 cfm or less is an LADBS Express Permit item, with no plan check.